Configure 'Motion sensor settings' prior to device commissioning

Created by Usha Nandhini, Modified on Wed, 15 Nov, 2023 at 5:51 AM by Usha Nandhini

  1. Choose the zone from the top right corner of the app
  2. Go to the 'Devices' tab in the app
  3. Click on the '+' button and choose the option 'Add Device'
  4. Click on 'Commissioning Settings' and choose 'Motion sensor settings'
  5. Choose the sensor activation period during which the light device should be respond on receiving motion sensor triggers 
    1. "When someone arrives": Defines the action to be performed when presence is detected
      1. Click on the iconfinder_Cog_4473007 icon to choose the intensity level to be maintained on detecting presence. The default value will be 100%
      2. Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec

    2. "When everybody leaves": Defines the action to be performed when absence is detected
      1. Configure the duration for which the lights should remain in the state configured for 'When someone arrives'. The default value will be 20 min and can be configured between  0.5 - 1023 min if 'Min' is chosen and 1-30 sec if 'Sec' is chosen
      2. Click on the iconfinder_Cog_4473007 icon to choose the intensity level to be maintained on detecting absence. The default value will be 0%
      3. Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec

    3. "Then": Defines the action to be performed later
      1. Configure the duration for which the lights should remain in the state configured for 'When everybody leaves'. The default value will be 20 min and can be configured between  0.5 - 1023 min if 'Min' is chosen and 1-30 sec if 'Sec' is chosen
      2. Click on the iconfinder_Cog_4473007 icon to choose the custom intensity level to be maintained later. The default value will be 0%
      3. Also, configure the duration within which the lights should attain the chosen state. The default value will be 1 sec and can be configured between 0-12.5 sec

    6. Enable the 'Manual override' option to configure the duration after which the light device should respond to the motion sensor triggers if it was manually controlled
    1. The default value for this interval is 10 sec and can be configured between 0-1270 sec

      Note: During this period the lights will not respond to the sensor

    You can also visit the following sections for more information:
    To know how to Commission & Configure Control Devices, click here
    To know how to Commission & Configure Sensors, click here
    To know how to Commission & Configure Switches, click here
    To know how to Commission & Configure Gateway, click here

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article