Emergency tests created in the mobile can only be configured at device level and cannot be done in groups. Only manual tests can be created from the mobile app. Internet connection is required so as to view the results of these tests in the Web UI.
- Go to the ‘Devices’ tab
- The icon of the DALI Controller will be in red to indicate that at least one of its child devices supports emergency lighting
- Click on the settings icon
- Select ‘Additional Settings’ and choose ‘Emergency Settings’
- Choose the target device which you wish to test
- Select the type of test to be done
- Function Test: A function test is a quick test that usually takes between a few seconds to 1 min to complete. This test checks the operation of the emergency light source from the battery supply and gives quick feedback on the device, battery and lamp statuses
- Duration Test: A duration test is a longer test which takes 1-3 hours and is usually carried out annually. This test can give feedback on the device’s current battery status, lamp status and ensures that the battery will be able to operate the lamp for the full rated duration
- Click on the ‘Start’ and enter a name for the test. This will immediately start the manual test. The test results will be available in the Web UI.
You can also visit the following sections for more information:
To know how to create Emergency Tests from the Web UI, click here
To know how does the Lumos Controls BMS integration work, click here
Was this article helpful?
That’s Great!
Thank you for your feedback
Sorry! We couldn't be helpful
Thank you for your feedback
Feedback sent
We appreciate your effort and will try to fix the article